The Series APM has a unique,
rugged, NEMA 4X front panel design that makes it nearly impenetrable in
typical applications. The weatherproof, UV resistant, large, dual line
display allows for more information making it easier to read and even
simpler to program. The intensity of the display can be adjusted
allowing this meter to be utilized in dark rooms as well as outdoors,
due to its sunlight readable display. It features up to eight visual
alarm set points to trigger certain events and three function keys which
can be programmed to provide direct menu access. With up to four relays
available, the APM features latching, nonlatching, sampling, pump
alteration control, and a fail-safe action. Offering programmable delay
time, this meter prevents recognition of false maximum or minimum
reading which may be caused by the start-up or unusual process events.
The APM provides three security passwords that restrict modification of
programmed settings. This unit has the ability to obtain non-linear
input signals and linearize them with simple to use math functions such
as square-root extractor, weirs and flumes exponential linearizer,
horizontal round tank linearizer or general purpose 32-point linearizer.
Unit accepts 0 to 20 mA, 4 to 20 mA, 0 to 5V, or ±10V inputs and
requires 85-265 VAC or 12/24 VDC power supply. Choose from RS-232,
RS-422/485 serial communication options or any available expansion
modules, accessories, and enclosures.
The APM is a 1/8 DIN digital panel meter specifically designed for
displaying flow rate and total from a flow meter with an analog output
such as 4 to 20 mA or 0 to 10V. The APM is particularly well-suited for
flow applications and can be programmed for a wide variety of display
configurations. The upper line can display either flow rate, total or
grand total, and the lower line can display either flow rate, total,
grand total, or engineering units. It is possible to display flow rate
and total at the same time, a very unique feature on a 1/8 DIN
digital panel meters.
Note: Shallow depth meters will not work with this Series.